  "id": "openplc-admin-race",
  "url": "https://ohshit.app/incidents/openplc-admin-race/",
  "title": "OpenPLC Runtime race condition permits unauthenticated administrator creation",
  "level": 3,
  "level_name": "sharted",
  "date": "2026-11-19",
  "date_is_approximate": false,
  "updated": null,
  "tags": [
    "OpenPLC",
    "ICS",
    "authentication bypass"
  ],
  "ecosystems": [],
  "summary": "CISA discloses CVE-2026-126088 in OpenPLC Runtime 4.2.4 and earlier. Concurrent requests can pass an account-existence check before any user is committed, creating unauthorized administrators. Upgrade to 4.3.0 or later.",
  "splash": "Network-reachable affected OpenPLC Runtime account-creation paths; exploitation requires a successful race.",
  "wipe": "Upgrade OpenPLC Runtime to 4.3.0 or later through an assessed maintenance plan; restrict control-network access.",
  "in_the_wild": "no",
  "source_exception": null,
  "cves": [
    {
      "id": "CVE-2026-126088",
      "score": 8.1,
      "name": "Administrator-creation race condition",
      "description": "Concurrent requests pass an existence check before a user is committed. CISA scores this 8.1 under CVSS 3.1 and 9.2 under CVSS 4.0; high attack complexity applies."
    }
  ],
  "fixed": [
    {
      "product": "OpenPLC Runtime 4.2.4 and earlier",
      "version": "4.3.0",
      "status": "CISA-listed corrective release"
    }
  ],
  "checklist": [
    {
      "title": "Plan and verify the runtime upgrade",
      "hint": "Inventory the running OpenPLC Runtime version and follow the vendor upgrade procedure to 4.3.0 or later. Assess process/safety impact, back up configuration and validate the running version and control behavior in an approved maintenance window."
    },
    {
      "title": "Reduce network exposure while patching",
      "hint": "CISA recommends keeping control systems off the public internet, isolating control networks from business networks and placing remote devices behind firewalls. Restrict management access to trusted sources; maintain any required VPN and its endpoints. Segmentation does not fix the race."
    },
    {
      "title": "Review administrator creation and investigate anomalies",
      "hint": "As a general response check, compare existing administrators with approved records and preserve available account-change/network logs before remediation. CISA provides no attack-specific IPs or signatures. Unexpected accounts need investigation; their absence does not prove no exposure. Follow your internal response process and report suspected malicious activity findings to CISA for tracking and correlation."
    }
  ],
  "sources": [
    {
      "name": "CISA ICSA-26-323-01 original advisory",
      "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-323-01",
      "says": "November 19 publication; versions through 4.2.4 affected, corrective version 4.3.0, CVSS scores, network isolation and change-impact guidance.",
      "primary": true
    },
    {
      "name": "CISA CNA CVE record",
      "url": "https://raw.githubusercontent.com/CVEProject/cvelistV5/main/cves/2026/126xxx/CVE-2026-126088.json",
      "says": "Confirms the existence-check race and publication date; does not establish real-world victims.",
      "primary": true
    }
  ],
  "headline": null,
  "one_liner": null,
  "in_the_wild_note": "CISA reports no known public exploitation at disclosure.",
  "mitigation": null,
  "timeline": [
    {
      "date": "Nov 19, 2026",
      "title": "CISA publishes ICSA-26-323-01",
      "body": "Lists the affected versions, 4.3.0 fix and absence of reported known public exploitation."
    }
  ],
  "body_markdown": "The check and the account commit are not synchronized: competing requests can each pass the existence check before the account write completes. Reachability and execution timing matter; this is not evidence that every already configured PLC has been taken over. CISA identifies industrial deployment sectors, not a count of affected facilities. No public exploitation is reported in the advisory. L3 reflects a remotely reachable administrator-creation flaw in an industrial runtime."
}